Prysmian · Australia

3CCUX6HDA · 150 mm²

Medium Voltage · 3.8/6.6 kV · 3-core copper

Illustrative 3D cable outside envelope
3D cable envelope
PlanAASection A–AOutside diameter 66.8 mm
2D general arrangement
Supply bus3-phase feeder1 × 3-core · 150 mm²
Electrical single-line representation

Datasheet

Product code
3CCUX6HDA
Rated voltage
3.8/6.6 kV
Conductor
3 × 150 mm² Copper
Insulation
XLPE
Armour
Armoured
Construction
heavy duty screened armoured
Outside diameter
66.8 mm
p. 42p. 43

Using this cable in a drawing

Use the published approximate outside diameter of 66.8 mm for the cable outline. The drawing shows a straight, illustrative run of 801.6 mm. Supports, terminations and installation clearances are project-specific. p. 43

Published current rating. 370 A · Direct buried, compacted backfill · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °C. p. 43p. 131

Download arrangement DXF · Symbol DXF · Editable 3D envelope

Compare a nearby size

Medium Voltage · Copper · 3.8/6.6 kV. Both columns use the publisher’s original units.

Parameter150 mm² · 3CCUX6HDA120 mm² · 3CCUX6HDA
Overall diameter66.8 mm63.4 mm
Cable weight940 kg/100 m830 kg/100 m
DC resistance0.124 Ω/km0.153 Ω/km
Current ratingDirect buried, compacted backfill · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °C370 A325 A
Current ratingSingleway duct, one cable per duct · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °C310 A280 A

Calculation parameters and conditions

ParameterValueManufacturer basisSource
Overall diameter66.8 mmApproximatep. 43
Cable weight940 kg/100 mApproximate massp. 43
DC resistance0.124 Ω/kmMaximum · conductor temperature 20 °Cp. 43
Minimum bend radius1200 mmDuring installation, PVCp. 43
AC resistance0.159 Ω/kmconductor temperature 90 °C · frequency 50 Hz · Three-core cablep. 43
Current rating370 ADirect buried, compacted backfill · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °Cp. 43p. 131
Current rating310 ASingleway duct, one cable per duct · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °Cp. 43p. 131

Source and files

Prysmian Medium Voltage Cables · 3CALX11HD · April 2015. Retrieved 2026-11-19.

Open manufacturer PDF · Search this PDF · Download datasheet PDF · Download typed JSON

SHA-256 4737d3bec581feeca321663725acccf526e1d307e2256e8038ebd1e0765a1a40
Design in 2D and 3D with AI

Design in 2D and 3D with AI

  • Create 2D and 3D from a description
  • Edit in plain words
  • Add equipment from this library
Try it on my own project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

Design my project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

“Create an electrical equipment layout with a switchboard, a generator and space for access.”
Design my project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

Design my project
3D electrical equipment layout