Prysmian · Australia

3CCUX6LD · 25 mm²

Medium Voltage · 3.8/6.6 kV · 3-core copper

Illustrative 3D cable outside envelope
3D cable envelope
PlanAASection A–AOutside diameter 38.3 mm
2D general arrangement
Supply bus3-phase feeder1 × 3-core · 25 mm²
Electrical single-line representation

Datasheet

Product code
3CCUX6LD
Rated voltage
3.8/6.6 kV
Conductor
3 × 25 mm² Copper
Insulation
XLPE
Armour
Unarmoured
Construction
light duty screened unarmoured
Outside diameter
38.3 mm
p. 36p. 37

Using this cable in a drawing

Use the published approximate outside diameter of 38.3 mm for the cable outline. The drawing shows a straight, illustrative run of 459.6 mm. Supports, terminations and installation clearances are project-specific. p. 37

Published current rating. 140 A · Direct buried, compacted backfill · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °C. p. 37p. 131

Download arrangement DXF · Symbol DXF · Editable 3D envelope

Compare a nearby size

Medium Voltage · Copper · 3.8/6.6 kV. Both columns use the publisher’s original units.

Parameter25 mm² · 3CCUX6LD35 mm² · 3CCUX6LD
Overall diameter38.3 mm40.5 mm
Cable weight170 kg/100 m210 kg/100 m
DC resistance0.727 Ω/km0.524 Ω/km
Current ratingDirect buried, compacted backfill · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °C140 A170 A
Current ratingSingleway duct, one cable per duct · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °C125 A140 A

Calculation parameters and conditions

ParameterValueManufacturer basisSource
Overall diameter38.3 mmApproximatep. 37
Cable weight170 kg/100 mApproximate massp. 37
DC resistance0.727 Ω/kmMaximum · conductor temperature 20 °Cp. 37
Minimum bend radius690 mmDuring installation, PVCp. 37
AC resistance0.927 Ω/kmconductor temperature 90 °C · frequency 50 Hz · Three-core cablep. 37
Current rating140 ADirect buried, compacted backfill · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °Cp. 37p. 131
Current rating125 ASingleway duct, one cable per duct · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °Cp. 37p. 131

Source and files

Prysmian Medium Voltage Cables · 3CALX11HD · April 2015. Retrieved 2026-11-19.

Open manufacturer PDF · Search this PDF · Download datasheet PDF · Download typed JSON

SHA-256 4737d3bec581feeca321663725acccf526e1d307e2256e8038ebd1e0765a1a40
Design in 2D and 3D with AI

Design in 2D and 3D with AI

  • Create 2D and 3D from a description
  • Edit in plain words
  • Add equipment from this library
Try it on my own project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

Design my project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

“Create an electrical equipment layout with a switchboard, a generator and space for access.”
Design my project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

Design my project
3D electrical equipment layout